Fluke 1623 GEO Earth Ground Testers
|
Our Price: Starting at $1,369.95
Manufacturer: FLUKE
Part Number: 1623
Product Options
| |
|
Fluke 1623 GEO Earth Ground Testers
Fluke 1623 Testing Methods:
-
3- and 4-Pole Fall of Potential – standard earth ground testing using two ground stakes
-
Selective testing – without disconnecting ground rods, a technician can measure ground resistance using a combination of stakes and a clamp.
-
Stakeless testing – innovative solution using only clamps, instead of ground stakes, to measure earth ground loop resistance.
Fluke 1623 Features:
-
One-button measurement concept
-
3- and 4-pole earth ground measurement
-
2-pole resistance measurement AC
-
Selective testing, no disconnection of ground conductor (1 clamp)
-
Stakeless testing, quick ground loop testing (2 clamps)
-
Measuring frequency 128 Hz
Fluke 1623 Environmental Specifications:
|
Working Temperature
|
-10 °C to +50 °C
|
|
Operating Temperature
|
0 °C to +35 °C
|
|
Nominal Temperature
|
+18 °C to +28°C
|
|
Storage Temperature
|
-20 °C to +60 °C
|
|
Climatic Class
|
C1 (IEC 654-1), -5 °C to +45 °C, 5 % to 95 % RH
|
|
Protection Type
|
IP56 for case. IP40 for battery door according to EN 60529
|
Fluke 1623 Mechanical & General Specifications:
|
Display
|
1999 digit LCD - display with special symbols, digit height 25mm,
fluorescent backlight
|
|
Size
|
133 mm x 187 mm x 250 mm
|
|
Weight
|
1.1 kg (including batteries)
|
|
Warranty
|
Two Years
|
|
Battery Life
|
Typical > 3000 measurements
|
Fluke 1623 RA 3-Pole Ground Resistance Measurement (IEC 1557-5):
|
Measuring Voltage
|
Vm = 48 V ac
|
|
Short Circuit Current
|
> 50 mA
|
|
Measure Frequency
|
128 Hz
|
|
Resolution
|
0.001 Ω to 10 Ω
|
|
Measuring Range
|
0.001 Ω to 19.99 kΩ
|
|
Intrinsic Error
|
± (2% of reading + 3 digit)
|
|
Operating Error
|
± (5% of reading + 3 d)
|
Fluke 1623 RA 4-Pole Ground Resistance Measurement (IEC 1557-5):
|
Measuring Voltage
|
Vm = 48 V ac
|
|
Short Circuit Current
|
> 50 mA
|
|
Measure Frequency
|
128 Hz
|
|
Resolution
|
0.001 Ω to 10 Ω
|
|
Measuring Range
|
0.001 Ω to 19.99 kΩ
|
|
Intrinsic Error
|
± (2% of reading + 3 d)
|
|
Operating Error
|
± (5% of reading + 3 d)
|
Fluke 1623 RA 3-Pole Ground Resistance Measurement with Current Clamp
|
Measuring Voltage
|
Vm = 48 V ac
|
|
Short Circuit Current
|
> 50 mA
|
|
Measure Frequency
|
128 Hz
|
|
Resolution
|
0.001 Ω to 10 Ω
|
|
Measuring Range
|
0.001 Ω to 19.99 kΩ
|
|
Intrinsic Error
|
± (7% of reading + 3d)
|
|
Operating Error
|
± (10% of reading + 5d)
|
Fluke 1623 RA 4-Pole Selective Ground Resistance Measurement with Current Clamp:
|
Measuring Voltage
|
Vm = 48 V ac
|
|
Short Circuit Current
|
> 50 mA
|
|
Measure Frequency
|
128 Hz
|
|
Resolution
|
0.001 Ω to 10 Ω
|
|
Measuring Range
|
0.001 Ω to 19.99 kΩ
|
|
Intrinsic Error
|
± (7% of reading + 3d)
|
|
Operating Error
|
± (10% of reading + 5d)
|
Fluke 1623 Stakeless Ground Loop Measurement:
|
Measuring Voltage
|
Vm = 48 V ac
|
|
Measure Frequency
|
128 Hz
|
|
Noise current (lext)
|
Max. Lext = 10 A (ac) (RA < 20 Ω)
Max. Lext = 2 A (ac) (RA < 20 Ω)
|
|
Resolution
|
0.001 Ω to 0.1 Ω
|
|
Measuring Range
|
0.001 Ω to 199.9 kΩ
|
|
Intrinsic Error
|
± (7% of reading + 3 d)
|
|
Operating Error
|
± (10% of reading + 5 d)
|
Fluke 1623 Includes:
-
Fluke 1623 tester
-
2 test leads
-
Batteries
-
Users manual
Fluke 1623 Kit Includes:
-
Fluke 1623 tester
-
2 test leads
-
4 earth ground stakes
-
3 cable reels with wire (2-25 m, 1-50 m)
-
2 clamps (one inducing, one sensing)
-
Batteries
-
Users Manual
-
Rugged Carrying Case
|
|
|
|


|
|