AEMC 4630 4-Point Ground Resistance Tester
Manufacturer: AEMC (Chauvin Arnoux)
Part Number: 2130.44
Product Options
* denotes required field
Optional AEMC 4620 Ground Test Kits*
NIST Calibration - Ground Tester*
|
|
AEMC 4630 4-Point Ground Resistance Tester
Digital Ground Resistance Tester Model 4630 perform both ground resistance and soil resistivity tests. This tester measures from 0 to 2000 Ohm , and are auto- ranging, so it automatically seek out the optimum measurement range. Easy-to-use: simply connect the leads, press-tomeasure and read the results. The large LCDs (nearly 3/4" high characters) are easy-to-read, and also indicate low battery status, overrange, test lead shorts and lead reversals. Three LED indicators on the front panel continuously warn the user of measurement problems to ensure accurate and reliable tests. The model 4630 is fuse protected up to >250Vac against accidental connection to live circuits. In the event of a system fault, they can withstand 250Vac with spikes of up to 3000Vac or 1000Vdc. The heavy-duty field case is sealed against dust and water when closed. The meter itself is self-contained within an inner case providing additional environmental and insulation protection. The test button is also sealed against the elements. The 4630 is powered by a 9.6V, 3.5 Ah NiMH rechargeable battery pack. A built-in recharge circuit, powered from 120/230V 50/60Hz line, also provides for testing while recharging. This model will perform over 2000- for the 15 second tests between recharging.The Ground Resistance Tester Model 4630 is rugged, easy-to-use instruments ideal for maintenance crews performing numerous tests. Both models exceed mechanical and safety specifications for shock, vibration and drop tests called out in IEC standards. They are designed to reject high levels of interference, so they can be used under difficult conditions such as high stray currents that normally affect accuracy.
Features:
-
Measures soil resistivity (4-Point) method
-
Measures ground resistance (2- and 3-Point) Fall-of-Potential method
-
Step voltage tests and touch potential measurements
-
Auto-Ranging: automatically selects the optimum resistance range
-
Designed to reject high levels of noise and interference
-
Extremely simple to operate: connect - press - read
-
LED on faceplate informs operator of high input noise, high auxiliary rod resistance and fault connections
-
Large easy-to-read backlit display
-
AC powered with rechargeable NiMH batteries
-
Rugged dustproof and rainproof field case
-
Can also be used for continuity tests on bonding
-
Color-coded terminals
-
Double Insulation
-
CE Mark
Applications:
-
Three-Point measurements of resistance to ground of ground rods and grids. Three-Point measurements are generally used when the electrode or grid can be easily disconnected, if corrosion is suspected, or in circumstances where ground faults are unlikely to occur.
-
Four-Point tests or soil resistivity measurements. Locating areas of lowest soil resistivity is essential for achieving an economical grounding installation.
-
Touch potential measurements, an alternative to 3-Point tests in evaluating electrical safety. This test is recommended when the ground cannot be disconnected, where ground faults are highly likely to occur, or when the footprint of grounded equipment (the outline of the part of equipment in contact with the earth) is comparable to the size of the ground to be tested.
-
Two-Point tests for continuity tests on bonding or on pre-established grounds. This test is commonly performed in urban environments where proper auxiliary electrode placement may be obscured by confined real estate. Measurements are referenced against a good local grounded circuit.
Specifications: 
|
The Analog Ground Resistance Tester Model 3620 performs ground resistance measurement from 0.5 to 1000Ω with speed and accuracy.
|
The Model 3640 comes with 3 color coded terminals to aid in easy hookup. Three LED indicators on the front panel continuously warn the user of measurement problems to ensure accurate and reliable tests.
|
The large LCD (nearly 3/4" high) also indicates low battery status, overrange, and test lead shorts and lead reversals. Three LED indicators on the front panel continuously warn user of measurement problems to ensure accurate and reliable tests.
|
The Digital Ground Resistance Tester performs ground resistance and soil resistivity tests.
|
|


|
|